Impacto de los armónicos de corriente en los transformadores de distribución monofásicos.
This study evaluates the impact that current harmonics generate in single-phase distribution transformers of 10, 15, 25 and 37.5 kVA, based on a data base of energy quality measurements for the years 2013, 2014 and 2015, Which were carried out by the Regional Electrical Company of South S. A and del...
Gespeichert in:
| 1. Verfasser: | |
|---|---|
| Format: | masterThesis |
| Sprache: | spa |
| Veröffentlicht: |
2017
|
| Schlagworte: | |
| Online Zugang: | http://dspace.unl.edu.ec/jspui/handle/123456789/18542 |
| Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
| _version_ | 1857833015527342080 |
|---|---|
| author | Aguilar Betancourt, Julia Patricia |
| author_facet | Aguilar Betancourt, Julia Patricia |
| author_role | author |
| collection | Repositorio Universidad Nacional de Loja |
| dc.contributor.none.fl_str_mv | Carrión González, Jorge Enrique |
| dc.creator.none.fl_str_mv | Aguilar Betancourt, Julia Patricia |
| dc.date.none.fl_str_mv | 2017-04-11T23:18:50Z 2017-04-11T23:18:50Z 2017 |
| dc.format.none.fl_str_mv | 91 p. application/pdf |
| dc.identifier.none.fl_str_mv | http://dspace.unl.edu.ec/jspui/handle/123456789/18542 |
| dc.language.none.fl_str_mv | spa |
| dc.rights.none.fl_str_mv | http://creativecommons.org/licenses/by-nc-sa/3.0/ec/ info:eu-repo/semantics/openAccess |
| dc.source.none.fl_str_mv | reponame:Repositorio Universidad Nacional de Loja instname:Universidad Nacional de Loja instacron:UNL |
| dc.subject.none.fl_str_mv | <TRANSFORMADORES DE DISTRIBUCIÓN MONOFÁSICOS><ARMÓNICOS DE CORRIENTE><NORMAS ANSI/IEEE C57. 110> <CLÚSTER><TÉCNICAS FUZZY CMEANS K-MEANS DENDOGRAMA> |
| dc.title.none.fl_str_mv | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| dc.type.none.fl_str_mv | info:eu-repo/semantics/publishedVersion info:eu-repo/semantics/masterThesis |
| description | This study evaluates the impact that current harmonics generate in single-phase distribution transformers of 10, 15, 25 and 37.5 kVA, based on a data base of energy quality measurements for the years 2013, 2014 and 2015, Which were carried out by the Regional Electrical Company of South S. A and delivered to carry out this study for educational purposes, being this base the starting point of the research. Current harmonics according to reviewed technical literature are those that generate an increase in energy losses and reduced capacity of transformers due to the high levels of non-linear currents caused by electronic loads. To establish the characteristic harmonic spectrum, methods and models were used aimed at seeking a typical harmonic behavior in the transformer, using mathematical tools employed in Matlab software, specifically mathematical tools, clustering analysis utilizing the FUZZY c-MEANS and k -MEANS techniques as well as a graphic dendrogram analysis. These techniques permitted the assessment of harmonic behavior in a time intervals and to establish its membership coefficient. To evaluate all monitored transformers with a characteristic harmonic spectrum, an analytical calculation model was proposed considering the technical recommendations put forward by the ANSI / IEEE C57.110 standard, determining the reduction of capacity and the allowable current of the transformer with respect to non-linear charges assuring that the highest losses do not exceed the value of the losses for which the transformer was designed considering that the transformer operates under normal conditions. The actual capacity that can be withstand and work each of the transformers of 10kVA 15 kVA 25 kVA and 37.5 kVA, will be 9.28 kVA, 13.91 kVA, 23.79 kVA and 34.60 kVA respectively. |
| eu_rights_str_mv | openAccess |
| format | masterThesis |
| id | UNL_c14e6a72bdc80e07a51207a2ce8873c4 |
| instacron_str | UNL |
| institution | UNL |
| instname_str | Universidad Nacional de Loja |
| language | spa |
| network_acronym_str | UNL |
| network_name_str | Repositorio Universidad Nacional de Loja |
| oai_identifier_str | oai:dspace.unl.edu.ec:123456789/18542 |
| publishDate | 2017 |
| reponame_str | Repositorio Universidad Nacional de Loja |
| repository.mail.fl_str_mv | * |
| repository.name.fl_str_mv | Repositorio Universidad Nacional de Loja - Universidad Nacional de Loja |
| repository_id_str | 0 |
| rights_invalid_str_mv | http://creativecommons.org/licenses/by-nc-sa/3.0/ec/ |
| spelling | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos.Aguilar Betancourt, Julia Patricia<TRANSFORMADORES DE DISTRIBUCIÓN MONOFÁSICOS><ARMÓNICOS DE CORRIENTE><NORMAS ANSI/IEEE C57. 110><CLÚSTER><TÉCNICAS FUZZY CMEANS K-MEANS DENDOGRAMA>This study evaluates the impact that current harmonics generate in single-phase distribution transformers of 10, 15, 25 and 37.5 kVA, based on a data base of energy quality measurements for the years 2013, 2014 and 2015, Which were carried out by the Regional Electrical Company of South S. A and delivered to carry out this study for educational purposes, being this base the starting point of the research. Current harmonics according to reviewed technical literature are those that generate an increase in energy losses and reduced capacity of transformers due to the high levels of non-linear currents caused by electronic loads. To establish the characteristic harmonic spectrum, methods and models were used aimed at seeking a typical harmonic behavior in the transformer, using mathematical tools employed in Matlab software, specifically mathematical tools, clustering analysis utilizing the FUZZY c-MEANS and k -MEANS techniques as well as a graphic dendrogram analysis. These techniques permitted the assessment of harmonic behavior in a time intervals and to establish its membership coefficient. To evaluate all monitored transformers with a characteristic harmonic spectrum, an analytical calculation model was proposed considering the technical recommendations put forward by the ANSI / IEEE C57.110 standard, determining the reduction of capacity and the allowable current of the transformer with respect to non-linear charges assuring that the highest losses do not exceed the value of the losses for which the transformer was designed considering that the transformer operates under normal conditions. The actual capacity that can be withstand and work each of the transformers of 10kVA 15 kVA 25 kVA and 37.5 kVA, will be 9.28 kVA, 13.91 kVA, 23.79 kVA and 34.60 kVA respectively.En este estudio se evalúa el impacto que generan los armónicos de corriente en los transformadores de distribución monofásicos de 10, 15, 25 y 37.5 kVA, tomando como referencia una base de datos de mediciones de calidad de energía de los años 2013, 2014 y 2015, las cuales fueron realizadas por la Empresa Eléctrica Regional del Sur S. A y entregadas para realizar este estudio con fines educativos, siendo esta base el punto de partida de la investigación. Los armónicos de corriente según la literatura técnica revisada son los que generan un incremento en las pérdidas de energía y la disminución de la capacidad de los transformadores debido a los altos niveles de corrientes no-lineales causadas por cargas electrónicas. Para determinar el espectro armónico característico se utilizaron métodos y modelos orientados a buscar un comportamiento armónico típico en el trasformador, haciendo uso de las herramientas matemáticas que posee el software Matlab, en particular las herramientas matemáticas, análisis clustering con la técnica FUZZY c-MEANS, k-MEANS y análisis gráfico por dendograma, estas técnicas permitieron evaluar el comportamiento armónico en un intervalo de tiempo y determinar su coeficiente de pertenencia. Para evaluar el conjunto de transformadores monitoreados con un espectro armónico característico se planteó un modelo de cálculo analítico considerando las recomendaciones técnicas expuestas en la norma ANSI/IEEE C57.110, determinándose la reducción de la capacidad y la corriente permisible del transformador ante cargas no-lineales ase¬gurando que las pérdidas más altas no superen el valor de las pérdidas para las cuales el transformador fue diseñado considerando que el transformador opera en condiciones normales. La capacidad real que pueden resistir y trabajar cada uno de los transformadores de 10kVA 15 kVA 25 kVA y el 37.5 kVA, será de 9,28 kVA, 13,91 kVA, 23,79 kVA y 34,60 kVA respectivamente.Carrión González, Jorge Enrique2017-04-11T23:18:50Z2017-04-11T23:18:50Z2017info:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesis91 p.application/pdfhttp://dspace.unl.edu.ec/jspui/handle/123456789/18542spahttp://creativecommons.org/licenses/by-nc-sa/3.0/ec/info:eu-repo/semantics/openAccessreponame:Repositorio Universidad Nacional de Lojainstname:Universidad Nacional de Lojainstacron:UNL2025-05-02T14:54:50Zoai:dspace.unl.edu.ec:123456789/18542Institucionalhttps://dspace.unl.edu.ec/Universidad públicahttps://unl.edu.ec/https://dspace.unl.edu.ec/oaiEcuador***opendoar:02025-05-02T14:54:50falseInstitucionalhttps://dspace.unl.edu.ec/Universidad públicahttps://unl.edu.ec/https://dspace.unl.edu.ec/oai*Ecuador***opendoar:02025-05-02T14:54:50Repositorio Universidad Nacional de Loja - Universidad Nacional de Lojafalse |
| spellingShingle | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. Aguilar Betancourt, Julia Patricia <TRANSFORMADORES DE DISTRIBUCIÓN MONOFÁSICOS><ARMÓNICOS DE CORRIENTE><NORMAS ANSI/IEEE C57. 110> <CLÚSTER><TÉCNICAS FUZZY CMEANS K-MEANS DENDOGRAMA> |
| status_str | publishedVersion |
| title | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| title_full | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| title_fullStr | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| title_full_unstemmed | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| title_short | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| title_sort | Impacto de los armónicos de corriente en los transformadores de distribución monofásicos. |
| topic | <TRANSFORMADORES DE DISTRIBUCIÓN MONOFÁSICOS><ARMÓNICOS DE CORRIENTE><NORMAS ANSI/IEEE C57. 110> <CLÚSTER><TÉCNICAS FUZZY CMEANS K-MEANS DENDOGRAMA> |
| url | http://dspace.unl.edu.ec/jspui/handle/123456789/18542 |