Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.

The present research consisted of simulating the insulators of the 69 kV Mulaló - La Cocha line through finite element analysis, to determine current leakage and its relationship with the ultrasound test due to conditions of loss of dielectric strength. For which field tests are carried out such as...

ver descrição completa

Na minha lista:
Detalhes bibliográficos
Autor principal: Herrera Naranjo, Estalin Gonzalo (author)
Formato: masterThesis
Idioma:spa
Publicado em: 2023
Assuntos:
Acesso em linha:http://repositorio.utc.edu.ec/handle/27000/10776
Tags: Adicionar Tag
Sem tags, seja o primeiro a adicionar uma tag!
_version_ 1822282061126303744
author Herrera Naranjo, Estalin Gonzalo
author_facet Herrera Naranjo, Estalin Gonzalo
author_role author
collection Repositorio Universidad Técnica de Cotopaxi
dc.contributor.none.fl_str_mv Mullo Quevedo, Álvaro Santiago
dc.creator.none.fl_str_mv Herrera Naranjo, Estalin Gonzalo
dc.date.none.fl_str_mv 2023-09-18T15:38:25Z
2023-09-18T15:38:25Z
2023
dc.format.none.fl_str_mv 94 páginas
dc.identifier.none.fl_str_mv Estalin Gonzalo Herrera Naranjo (2023); Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de pérdida de rigidez dieléctrica. UTC. Latacunga. 94 p.
MUTC-001710
http://repositorio.utc.edu.ec/handle/27000/10776
dc.language.none.fl_str_mv spa
dc.publisher.none.fl_str_mv Ecuador: Latacunga: Universidad Técnica de Cotopaxi,(UTC)
dc.rights.none.fl_str_mv http://creativecommons.org/licenses/by-nc-sa/3.0/ec/
info:eu-repo/semantics/openAccess
dc.source.none.fl_str_mv reponame:Repositorio Universidad Técnica de Cotopaxi
instname:Universidad Técnica de Cotopaxi
instacron:UTC
dc.subject.none.fl_str_mv AISLADORES
ULTRASONIDO
SIMULACIÓN
MÉTODO DE ELEMENTOS FINITOS
ELÉCTRICA
dc.title.none.fl_str_mv Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
dc.type.none.fl_str_mv info:eu-repo/semantics/publishedVersion
info:eu-repo/semantics/masterThesis
description The present research consisted of simulating the insulators of the 69 kV Mulaló - La Cocha line through finite element analysis, to determine current leakage and its relationship with the ultrasound test due to conditions of loss of dielectric strength. For which field tests are carried out such as visual inspection, ultrasound and thermography. The applied methodology consisted of a field study through the use of technological equipment to determine the state of the insulators and the environmental conditions, in which pollution incrustation and fissures were found, that with the thermography equipment is observed that in the phase R maintains a temperature of 76C that shows an electrical tracking of high frequencies and amplitudes that is out of the conditions to be intervened in immediate maintenance, in phase S a temperature of 44.8C with a stable ultrasound tracking under normal conditions and in phase T, a temperature of 59C with irregular ultrasound frequencies is therefore recommended to make an immediate change. According to the modeling with the FEMM software, the dynamic evaluation was carried out where in Phase R there is a current leakage of 30 A/m2, in phase S a leakage of 3.2 A/m2 and in T a leakage of 200 A/m2. m2. The same one that determines that there is a relationship between the current leakage and the superficial deterioration of the insulators and an increase in the frequency and amplitude of the ultrasound test.
eu_rights_str_mv openAccess
format masterThesis
id UTC_066869e00a9f595c6644914934576669
identifier_str_mv Estalin Gonzalo Herrera Naranjo (2023); Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de pérdida de rigidez dieléctrica. UTC. Latacunga. 94 p.
MUTC-001710
instacron_str UTC
institution UTC
instname_str Universidad Técnica de Cotopaxi
language spa
network_acronym_str UTC
network_name_str Repositorio Universidad Técnica de Cotopaxi
oai_identifier_str oai:oai:repositorio.utc.edu.ec:27000:27000/10776
publishDate 2023
publisher.none.fl_str_mv Ecuador: Latacunga: Universidad Técnica de Cotopaxi,(UTC)
reponame_str Repositorio Universidad Técnica de Cotopaxi
repository.mail.fl_str_mv .
repository.name.fl_str_mv Repositorio Universidad Técnica de Cotopaxi - Universidad Técnica de Cotopaxi
repository_id_str 0
rights_invalid_str_mv http://creativecommons.org/licenses/by-nc-sa/3.0/ec/
spelling Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.Herrera Naranjo, Estalin GonzaloAISLADORESULTRASONIDOSIMULACIÓNMÉTODO DE ELEMENTOS FINITOSELÉCTRICAThe present research consisted of simulating the insulators of the 69 kV Mulaló - La Cocha line through finite element analysis, to determine current leakage and its relationship with the ultrasound test due to conditions of loss of dielectric strength. For which field tests are carried out such as visual inspection, ultrasound and thermography. The applied methodology consisted of a field study through the use of technological equipment to determine the state of the insulators and the environmental conditions, in which pollution incrustation and fissures were found, that with the thermography equipment is observed that in the phase R maintains a temperature of 76C that shows an electrical tracking of high frequencies and amplitudes that is out of the conditions to be intervened in immediate maintenance, in phase S a temperature of 44.8C with a stable ultrasound tracking under normal conditions and in phase T, a temperature of 59C with irregular ultrasound frequencies is therefore recommended to make an immediate change. According to the modeling with the FEMM software, the dynamic evaluation was carried out where in Phase R there is a current leakage of 30 A/m2, in phase S a leakage of 3.2 A/m2 and in T a leakage of 200 A/m2. m2. The same one that determines that there is a relationship between the current leakage and the superficial deterioration of the insulators and an increase in the frequency and amplitude of the ultrasound test.La presente investigación consistió en simular los aisladores de la línea de 69 kV Mulaló – La Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica. Para lo cual se realización ensayos de campo como inspección visual, ultrasonido y termografía. La metodología aplicada consistía en un estudio de campo mediante uso de equipos tecnológicos para determinar el estado de los aisladores y las condiciones ambientales, en los mismos que se encontraron incrustación de polución y fisuras, que con el equipo de termografía se observa que en la fase R mantiene una temperatura de 76C que aparece un traking eléctricos de altas frecuencias y amplitudes que se encuentra fuera de las condiciones para que sea intervenido en mantenimiento inmediato, en la fase S una temperatura de 44.8C con un traking de ultrasonido estable se encuentra en condiciones normales y en la fase T una temperatura de 59C con frecuencias de ultrasonido irregulares por lo que se recomienda realizar un cambio inmediato. De acuerdo a la modelación con el software FEMM se procedió a la evaluación dinámica donde en la Fase R posee una fuga de corriente 30 A/m2 en la fase S una fuga de 3.2 A/m2 y en la T una fuga de 200 A/m2. La misma que determina que existe una relación entre la fuga de corriente y el deterioro superficial de los aisladores y un aumento en la frecuencia y amplitud del ensayo de ultrasonido.Ecuador: Latacunga: Universidad Técnica de Cotopaxi,(UTC)Mullo Quevedo, Álvaro Santiago2023-09-18T15:38:25Z2023-09-18T15:38:25Z2023info:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesis94 páginasEstalin Gonzalo Herrera Naranjo (2023); Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de pérdida de rigidez dieléctrica. UTC. Latacunga. 94 p.MUTC-001710http://repositorio.utc.edu.ec/handle/27000/10776spahttp://creativecommons.org/licenses/by-nc-sa/3.0/ec/info:eu-repo/semantics/openAccessreponame:Repositorio Universidad Técnica de Cotopaxiinstname:Universidad Técnica de Cotopaxiinstacron:UTC2023-09-19T08:00:27Zoai:oai:repositorio.utc.edu.ec:27000:27000/10776Institucionalhttp://repositorio.utc.edu.ec/Universidad públicahttps://www.utc.edu.ec/..Ecuador...opendoar:02025-01-26T03:45:52.036791Repositorio Universidad Técnica de Cotopaxi - Universidad Técnica de Cotopaxitrue
spellingShingle Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
Herrera Naranjo, Estalin Gonzalo
AISLADORES
ULTRASONIDO
SIMULACIÓN
MÉTODO DE ELEMENTOS FINITOS
ELÉCTRICA
status_str publishedVersion
title Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
title_full Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
title_fullStr Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
title_full_unstemmed Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
title_short Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
title_sort Modelamiento de los aisladores de la línea de 69kv Mulalo - la Cocha mediante análisis de elementos finitos, para determinar las fugas de corriente y su relación con el ensayo de ultrasonido a causa de condiciones de perdida de rigidez dieléctrica.
topic AISLADORES
ULTRASONIDO
SIMULACIÓN
MÉTODO DE ELEMENTOS FINITOS
ELÉCTRICA
url http://repositorio.utc.edu.ec/handle/27000/10776