Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.

This research work deals with the analysis of the shielding and grounding systems in the GasgreBiogas Plant because failures have occurred there, causing damage to the protection equipment in turn ihas been considered a future expansion. Thus, soil resistivity andgrounding resistance measurements we...

Πλήρης περιγραφή

Αποθηκεύτηκε σε:
Λεπτομέρειες βιβλιογραφικής εγγραφής
Κύριος συγγραφέας: Changoluisa Chacha, Cristian Javier (author)
Άλλοι συγγραφείς: Monga Sánchez, Diego Paúl (author)
Μορφή: masterThesis
Γλώσσα:spa
Έκδοση: 2021
Θέματα:
Διαθέσιμο Online:http://repositorio.utc.edu.ec/handle/27000/7798
Ετικέτες: Προσθήκη ετικέτας
Δεν υπάρχουν, Καταχωρήστε ετικέτα πρώτοι!
_version_ 1859064028107636736
author Changoluisa Chacha, Cristian Javier
author2 Monga Sánchez, Diego Paúl
author2_role author
author_facet Changoluisa Chacha, Cristian Javier
Monga Sánchez, Diego Paúl
author_role author
collection Repositorio Universidad Técnica de Cotopaxi
dc.contributor.none.fl_str_mv Salazar, Edgar
dc.creator.none.fl_str_mv Changoluisa Chacha, Cristian Javier
Monga Sánchez, Diego Paúl
dc.date.none.fl_str_mv 2021-12-07T19:52:30Z
2021-12-07T19:52:30Z
2021-07
dc.format.none.fl_str_mv 111 páginas
application/pdf
dc.identifier.none.fl_str_mv Changoluisa Chacha Cristian Javier, Monga Sánchez Diego Paúl ( 2021), Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito. UTC. Latacunga. 111 p.
MUTC-001008
http://repositorio.utc.edu.ec/handle/27000/7798
dc.language.none.fl_str_mv spa
dc.publisher.none.fl_str_mv Ecuador: Latacunga: Universidad Técnica de Cotopaxi: UTC.
dc.rights.none.fl_str_mv http://creativecommons.org/licenses/by-nc-sa/3.0/ec/
info:eu-repo/semantics/openAccess
dc.source.none.fl_str_mv reponame:Repositorio Universidad Técnica de Cotopaxi
instname:Universidad Técnica de Cotopaxi
instacron:UTC
dc.subject.none.fl_str_mv COORDINACIÓN DE AISLAMIENTO
APANTALLAMIENTO ELÉCTRICO
SISTEMA DE PUESTA A TIERRA
SOBREVOLTAJES
ELECTRICIDAD
dc.title.none.fl_str_mv Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
dc.type.none.fl_str_mv info:eu-repo/semantics/publishedVersion
info:eu-repo/semantics/masterThesis
description This research work deals with the analysis of the shielding and grounding systems in the GasgreBiogas Plant because failures have occurred there, causing damage to the protection equipment in turn ihas been considered a future expansion. Thus, soil resistivity andgrounding resistance measurements were madtobtain values of up to 40.4 Ω-m and 986 Ω, respectively. Therefore, the systems were modeled in ETAP in initial and current conditions with the present value of soil resistivity 23.57 Ω-m. Besides, it determined the resistance of 0.588 Ω, a touch voltage of 854.4 V. It exceeded the tolerable values. Also, according to the modeling of the rolling spheres for the current shielding system made up of a dipole type lightning rod, it was determined the second stage of generators are outside the protection zone andupon expansion. This set of protections would not provide the necessary guarantees for the proper functioning of the plant. Improvements to the system were proposed that were verified by software. So, It got grounding values of 0.414 Ω and a touching voltage of 589 V. They are within thepermissible limits; in addition, to designing the third stage of the same. While for the modeled shielding system, it is suggested to use two piezoelectric lightning rods with a delta of 10 meters and a diameter to cover aleast 80 meters for the entire plant.
eu_rights_str_mv openAccess
format masterThesis
id UTC_ddb6cdb708cb5a6a9a5bb9c0871d3be2
identifier_str_mv Changoluisa Chacha Cristian Javier, Monga Sánchez Diego Paúl ( 2021), Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito. UTC. Latacunga. 111 p.
MUTC-001008
instacron_str UTC
institution UTC
instname_str Universidad Técnica de Cotopaxi
language spa
network_acronym_str UTC
network_name_str Repositorio Universidad Técnica de Cotopaxi
oai_identifier_str oai:repositorio.utc.edu.ec:27000/7798
publishDate 2021
publisher.none.fl_str_mv Ecuador: Latacunga: Universidad Técnica de Cotopaxi: UTC.
reponame_str Repositorio Universidad Técnica de Cotopaxi
repository.mail.fl_str_mv .
repository.name.fl_str_mv Repositorio Universidad Técnica de Cotopaxi - Universidad Técnica de Cotopaxi
repository_id_str 0
rights_invalid_str_mv http://creativecommons.org/licenses/by-nc-sa/3.0/ec/
spelling Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.Changoluisa Chacha, Cristian JavierMonga Sánchez, Diego PaúlCOORDINACIÓN DE AISLAMIENTOAPANTALLAMIENTO ELÉCTRICOSISTEMA DE PUESTA A TIERRASOBREVOLTAJESELECTRICIDADThis research work deals with the analysis of the shielding and grounding systems in the GasgreBiogas Plant because failures have occurred there, causing damage to the protection equipment in turn ihas been considered a future expansion. Thus, soil resistivity andgrounding resistance measurements were madtobtain values of up to 40.4 Ω-m and 986 Ω, respectively. Therefore, the systems were modeled in ETAP in initial and current conditions with the present value of soil resistivity 23.57 Ω-m. Besides, it determined the resistance of 0.588 Ω, a touch voltage of 854.4 V. It exceeded the tolerable values. Also, according to the modeling of the rolling spheres for the current shielding system made up of a dipole type lightning rod, it was determined the second stage of generators are outside the protection zone andupon expansion. This set of protections would not provide the necessary guarantees for the proper functioning of the plant. Improvements to the system were proposed that were verified by software. So, It got grounding values of 0.414 Ω and a touching voltage of 589 V. They are within thepermissible limits; in addition, to designing the third stage of the same. While for the modeled shielding system, it is suggested to use two piezoelectric lightning rods with a delta of 10 meters and a diameter to cover aleast 80 meters for the entire plant.El presente trabajo de investigación trata el análisis de los sistemas de apantallamiento y puesta a tierra en la Central de Biogás Gasgreen, debido a que en la misma se han suscitado fallas, ocasionando daños en los equipos de protección, a su vez se a considerado una futura expansión. Para lo cual se realizaron mediciones de resistividad del suelo y resistencia de puesta a tierra, obteniéndose valores de hasta 40,4 Ω-m y 986 Ω respectivamente. Posteriormente se modeló los sistemas en ETAP; en condiciones iniciales y actuales con el valor presente de resistividad del suelo 23,57 Ω-m, determinándose una resistencia de 0,588 Ω, un voltaje de toque de 854,4 V, el cual excede los valores tolerables, así también acorde al modelamiento de las esferas rodantes para el sistema de apantallamiento actual conformado por un pararrayo tipo dipolo; se determinó que la segunda etapa de generadores se encuentran fuera de la zona de protección y al efectuarse una expansión este conjunto de protecciones no prestarían las garantías necesarias para el buen funcionamiento de la central. Se plantearon mejoras al sistema; las cuales se comprobaron mediante software; obteniéndose valores de puesta a tierra de 0,414 Ω y voltaje de toque de 589 V los cuales están dentro de los límites permisibles, además de diseñarse la tercera etapa del mismo. Mientras que para el sistema de apantallamiento modelado se sugiere utilizar dos pararrayos piezoeléctricos con un delta de 10 metros y un diámetro a cubrir como mínimo 80 metros para toda la central.Ecuador: Latacunga: Universidad Técnica de Cotopaxi: UTC.Salazar, Edgar2021-12-07T19:52:30Z2021-12-07T19:52:30Z2021-07info:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesis111 páginasapplication/pdfChangoluisa Chacha Cristian Javier, Monga Sánchez Diego Paúl ( 2021), Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito. UTC. Latacunga. 111 p.MUTC-001008http://repositorio.utc.edu.ec/handle/27000/7798spahttp://creativecommons.org/licenses/by-nc-sa/3.0/ec/info:eu-repo/semantics/openAccessreponame:Repositorio Universidad Técnica de Cotopaxiinstname:Universidad Técnica de Cotopaxiinstacron:UTC2021-12-08T08:00:40Zoai:repositorio.utc.edu.ec:27000/7798Institucionalhttp://repositorio.utc.edu.ec/Universidad públicahttps://www.utc.edu.ec/..Ecuador...opendoar:02026-03-08T03:37:29.569596Repositorio Universidad Técnica de Cotopaxi - Universidad Técnica de Cotopaxitrue
spellingShingle Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
Changoluisa Chacha, Cristian Javier
COORDINACIÓN DE AISLAMIENTO
APANTALLAMIENTO ELÉCTRICO
SISTEMA DE PUESTA A TIERRA
SOBREVOLTAJES
ELECTRICIDAD
status_str publishedVersion
title Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
title_full Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
title_fullStr Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
title_full_unstemmed Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
title_short Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
title_sort Análisis del sistema de puesta a tierra y apantallamiento eléctrico, mediante modelamiento en software para garantizar el funcionamiento y desempeño de las instalaciones, considerando una futura expansión en la central de generación “GASGREEN S.A.”, ubicada en el relleno sanitario del Distrito Metropolitano de Quito.
topic COORDINACIÓN DE AISLAMIENTO
APANTALLAMIENTO ELÉCTRICO
SISTEMA DE PUESTA A TIERRA
SOBREVOLTAJES
ELECTRICIDAD
url http://repositorio.utc.edu.ec/handle/27000/7798